Fault Status 3 Report Mask
[Flt Report Mask 3]

This parameter selects the faults that can be
reported to P180.

1 - Report

0 - Suppress

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1111 1111 1111 1111

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P180, P181

Bit

Description

Bit

Description

0

Clock Loss

Reports when the oscillator clock is lost.

8*

DPRAM Error

Reports errors in the DPRAM.

1

Double Bus

Reports memory access errors.

9

No Vloop Tic

Reports when the voltage loop clock is lost.

2

Watchdog

Reports when the watchdog timer is expired.

10*

No Fast Task

Reports when high speed tasks are not executing.

3

En at Pwr Up

Reports when the RGU is Enabled at power up.

11*

No Bgnd Task

Reports when background tasks are not running.

4

Battery Low

Reports when the BRAM battery is low.

12*

Addr Bus Err

Reports address bus errors.

5*

TIO Loss

Reports when the primary clock is lost.

13*

Data Bus Err

Reports data bus errors.

6*

R2R Dup Addr

Reports when RGUs have an address conflict.

14

Line Low

Reports when the AC line voltage falls below P26.

7*

Lost Master

Reports when Master communication is lost.

15

Line High

Reports when the AC line voltage exceeds P27.

* These items cannot be changed to zero.

182

Fault/Warning Select Mask 3
[Fault/Warn Mask3]

This parameter determines whether conditions
should be reported as a warning (0) or handled as
a fault (1).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0011 1101 1110 1000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P180, P181

Bit

Description

Bit

Description

0

Clock Loss

Selects response to a lost clock.

8*

DPRAM Error

Selects response to DPRAM errors.

1

Double Bus

Selects response to memory access errors.

9

No Vloop Tic

Selects response to voltage loop timer errors.

2

Watchdog

Selects response to watchdog timer expiration.

10*

No Fast Task

Selects response to fast task lockup.

3

En at Pwr Up

Selects response when RGU Enables at pwr up.

11*

No Bgnd Task

Selects response to background task lockup.

4

Battery Low

Selects response to low BRAM battery voltage.

12*

Addr Bus Err

Selects response to address bus errors.

5*

TIO Loss

Selects response to primary clock being lost.

13*

Data Bus Err

Selects response to data bus errors.

6*

R2R Dup Addr

Selects response to duplicate address errors.

14

Line Low

Selects response to low voltage in the AC line.

7*

Lost Master

Selects response to losing the Master.

15

Line High

Selects response to high voltage in the AC line.

* These items cannot be changed to zero.

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7