Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 155

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-11

38

A/D Converter 2 Input
[14 Bit A/D Chan 2]

This parameter receives an analog-to-digital
sample from the DC bus to provide the value for
the Scaled Bus Feedback (P143).

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-8191 (-10V signal)

Maximum Value

8191 (+10V signal)

Related Parameters

P139, P143

This parameter is sent to P143 when

Host Channel is selected in the Bus Voltage
Input Select (P139 = 2).

The listing for P36 shows a quick reference
chart for converting the display value into
the analog input voltage.

39

A/D Converter 3 Input
[14 Bit A/D Chan 3]

This parameter receives an analog-to-digital
sample from the negative DC bus and PE to
provide the value for P146 (Negative DC Bus To
Ground Voltage).

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-8191 (-10V signal)

Maximum Value

8191 (+10V signal)

Related Parameters

P146

The listing for P36 shows a quick reference
chart for converting the display value into
the analog input voltage.

40

A/D Converter 4 Input
[14 Bit A/D Chan 4]

This parameter receives an analog-to-digital
sample from the positive DC bus and PE to
provide the value for P145 (Positive DC Bus To
Ground Voltage).

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-8191 (-10V signal)

Maximum Value

8191 (+10V signal)

Related Parameters

P145

The listing for P36 shows a quick reference
chart for converting the display value into
the analog input voltage.

41

A/D Converter 5 Input
[14 Bit A/D Chan 5]

This parameter receives an analog-to-digital
sample from the AC line to provide the value for
P14 (Measured AC Line Voltage).
The listing for P36 shows a quick reference chart
for converting the display value into the analog
input voltage.

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-8191 (-10V signal)

Maximum Value

8191 (+10V signal)

Related Parameters

P14

42

A/D Converter 6 Input
[14 Bit A/D Chan 6]

This parameter receives an analog-to-digital
sample from the AC line (composite line voltage)
to provide the value for P14 (Measured AC Line
Voltage).

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-8191 (-10V signal)

Maximum Value

8191 (+10V signal)

Related Parameters

P14

The listing for P36 shows a quick reference
chart for converting the display value into
the analog input voltage.