Adjusting Voltage and Current Regulation Parameters

1. Set P219 to “0” for normal operation (this value cannot be

changed while the unit is running).

2. Select values for Wn (P137) between 0 and 32767 radians/

second, and Kn (P138) between 0 and 1 of the feedback filter.

3. P141 contains the final DC bus feedback value.

Comparing the DC Bus Reference with the DC Bus Feedback

As shown in Figure 9.5, the error signal is the difference between the
DC bus reference (P128) and the DC bus feedback (P141).

Figure 9.5
Firmware Diagram for Comparing the DC Bus Reference with the DC Bus
Feedback

128

+

-

141

DC Bus Reference

DC Bus Feedback

Error Signal

X

X

Y

X

X

X

*

Indirect, parameter X

Source; parameter X

Sink; parameter X

Parameter X, bit Y

Battery-backed, parameter X

SYMBOL KEY

142

Parameter Number

Parameter Name

128

Bus Reference

141

Bus Feedback

142

Voltage Loop Error