Adjusting Voltage and Current Regulation Parameters
1. Set P219 to “0” for normal operation (this value cannot be
changed while the unit is running).
2. Select values for Wn (P137) between 0 and 32767 radians/
second, and Kn (P138) between 0 and 1 of the feedback filter.
3. P141 contains the final DC bus feedback value.
Comparing the DC Bus Reference with the DC Bus Feedback
As shown in Figure 9.5, the error signal is the difference between the
DC bus reference (P128) and the DC bus feedback (P141).
Figure 9.5
Firmware Diagram for Comparing the DC Bus Reference with the DC Bus
Feedback
128
+
-
141
DC Bus Reference
DC Bus Feedback
Error Signal
X
X
Y
X
X
X
*
Indirect, parameter X
Source; parameter X
Sink; parameter X
Parameter X, bit Y
Battery-backed, parameter X
SYMBOL KEY
142
Parameter Number
Parameter Name
128
Bus Reference
141
Bus Feedback
142
Voltage Loop Error