Programming Parameters

D-23

103

Id Mode Select
[Id Mode Select]

This parameter selects the Id current reference to
be sent to the Id limiter.

Select the Id limiter input from the list below.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

3

Related Parameters

P93, P101, P102

104

Id Positive Current Limit
[Id Pos Limit]

This parameter determines the maximum value for
the Id Reference (P93). The value of this
parameter is passed to the Id limiter.

This parameter is selected as the source to the

Parameter Type

Sink (Read/Write)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

60.0

Minimum Value

0.0

Maximum Value

60.0

Related Parameters

P35, P93, P105

Id limiter when P35 bit 0 = 0 (when the Host Mode,
Regen Only bit is set to zero). This limit
is selected by default.

When P35 bit 0 = 1, this parameter is not used,
and a value of 0% is passed to the Id limiter.

105

Id Negative Current Limit
[Id Neg Limit]

This parameter determines the minimum value for
the Id Reference (P93). The value of this
parameter is passed to the Id limiter.

Parameter Type

Sink (Read/Write)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

-40.0

Minimum Value

-40.0

Maximum Value

0

Related Parameters

P93, P104

106

Id Current Feedback
[Id Feedback]

This parameter displays the calculated Id
feedback.

The value of this parameter is used with P100 (Iq
Feedback) and P11 (Rated AC Line Current) to
calculate the Total Line Current (P108).

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-60.0

Maximum Value

60.0

Related Parameters

P93, P100, P108

The value is also used (with P100) to trigger
the wire overload (I2t) indicators (P34 and P183).

P103

Id Mode

Select

P101

Auxiliary Id

Command

0

+

+

0

1

2

3

None

Id Command

Aux Id Cmd

Id Cmd + Aux

0

1

2

3

P102

Id Current
Command

Σ

Id Limiter

Value Description

0

None

Selects 0% as the input to the Id limiter.

1

Id Command

Selects the value in P102 (Id Command) as the input
to the Id limiter.

2

Aux Id Cmd

Selects the value in P101 (Auxiliary Id Command) as
the input to the Id limiter.

3

Id Cmd + Aux Selects the sum of P102 (Id Command) and P101

(Auxiliary Id Command) as the input to the Id limiter.

Advertising