Publication 2364F-5.01– October 2003

D-30

Programming Parameters

141

Bus Feedback
[Bus Feedback]

This parameter displays the value of the bus
feedback. This bus feedback value is compared
with the Bus Reference (P128) to determine the
bus error (P142) which needs to be corrected by
the PI regulator.

Parameter Type

Sink (Read Only)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0

Minimum Value

0

Maximum Value

1.5 x P16

Related Parameters

P128, P140, P142

142

Voltage Loop Error
[Bus Error]

This parameter shows the error in the DC bus that
needs to be corrected through the PI regulator.
This value is used to adjust the bus voltage
(shown by the Bus Feedback (P141)) to the
commanded voltage (shown by the Bus
Reference (P128)).

Parameter Type

Sink (Read Only)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0

Minimum Value

0

Maximum Value

1.5 x P16

Related Parameters

P128, P140, P142

143

Scaled Bus Feedback
[Scaled Bus Fbk]

This parameter shows the calibrated bus
feedback. The value of this parameter is used to
determine the Bus Feedback (P141) and is used
to calculate the DC Bus Current (P107).

Parameter Type

Source (Read Only)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0

Minimum Value

0

Maximum Value

1.5 x P16

Related Parameters

P38, P60, P61, P144

144

Bus Voltage Feedback Calibration
[Bus Volt Cal]

This parameter is used to adjust the voltage value
shown in the bus feedback parameters (i.e. P140,
P141, P143).

To calibrate the feedback, adjust this parameter
until P143 (Scaled Bus Feedback) is equal to the

Parameter Type

Sink (Read/Write)

Display Units

% of P143

Drive Units

Display Units * 1125/1000

Factory Default

0.0

Minimum Value

-3.1

Maximum Value

3.1

Related Parameters

P141, P143

voltage of the DC bus (use a voltmeter). This
parameter can only be set when the RGU is
Disabled.

145

Positive DC Bus to Ground Voltage
[+Bus Volt to Gnd]

This parameter indicates the voltage between the
positive DC bus and the ground (PE).

P40 (A/D Converter 4 Input) supplies the raw data
for this parameter.

Parameter Type

Source (Read Only)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0

Minimum Value

0

Maximum Value

1.15 x P16

Related Parameters

P40, P146

146

Negative DC Bus to Ground Voltage
[-Bus Volt to Gnd]

This parameter indicates the voltage between the
negative DC bus and the ground (PE).

P39 (A/D Converter 3 Input) supplies the raw data
for this parameter.

Parameter Type

Source (Read Only)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0

Minimum Value

0

Maximum Value

1.15 x P16

Related Parameters

P39, P145

Σ

PI Regulator

+

_

P142

Voltage

Loop Error

P141

Bus

Feedback

P128

Bus

Reference