Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 170

Advertising
background image

Publication 2364F-5.01– October 2003

D-26

Programming Parameters

121

Voltage Loop PI Output
[PI Reg Out]

This parameter stores the output from the PI
regulator. When the P90 (Iq Mode) equals 0 or 1,
this value is passed through the current limiter to
determine the Iq Reference (P96).

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-640.0

Maximum Value

640.0

Related Parameters

P90, P96, P118, P119, P120

The diagram shows how the PI regulator is
arranged, and shows how the value for P121 is
determined.

See the P90 listing for more information about
this parameter.

122

Auxiliary Voltage Command
[Aux Volt Cmd]

This parameter defines an auxiliary voltage that
can be commanded for the DC bus. The value
entered into this parameter can be used to
command a specific bus voltage (when P123 = 1)
or can be used to add to the Bus Voltage
Command in P207 (when P123 = 2).

Parameter Type

Sink (Read/Write)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0

Minimum Value

-1.15 x P16

Maximum Value

1.15 x P16

Related Parameters

P123, P126, P207

To use this parameter as an auxiliary bus voltage,

To use this parameter as a supplement to the

enter the bus voltage that is needed during

Bus Voltage Command (P207) during particular

particular events then program P123 to equal 1

events, enter the bus voltage to be added to P207

during those events.

and program P123 to equal 2 during those events.

PI Regulator

w/ Error Limiter

P121

Voltage
Loop PI

Output

Σ

P142

Voltage

Loop Error

P118

Voltage Loop

Proportional

Gain

P119

Voltage Loop
Integral Gain

Error Limiter

P116

P117

P115

Prop
Gain

Integral

Gain

P94

Iq

Reference

+

+

+

P120

Voltage Loop

Integrator

Output