Publication 2364F-5.01– October 2003

Programming Parameters

D-19

85

P85 is for internal use only.

86

Transistor Junction Temperature
[Abs Junct Temp]

This parameter indicates the calculated IGBT
junction temperature. This value is used by the
fault status parameters to indicate when high and
excessive temperatures occur.

Parameter Type

Source (Read Only)

Display Units

degC

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-50

Maximum Value

150

87

Heatsink Temperature
[Heatsink Temp]

This parameter indicates the measured heatsink
temperature. This value is used by the fault status
parameters to indicate when high and excessive
temperatures occur.

Parameter Type

Source (Read Only)

Display Units

degC

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-50

Maximum Value

127

88

Auxiliary Iq Current Limit
[Aux Iq Limit]

This parameter specifies the limit imposed on P89
(Auxiliary Iq Current Command).

The value of this parameter (current limit) is
displayed as a percentage of the Rated AC Line
Current (P11).

Parameter Type

Sink (Read/Write)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

150.0

Minimum Value

0.0

Maximum Value

150.0

Related Parameters

P11, P89

This parameter is only activated when Aux
Limit is selected in Host Mode (P35 bit 2 = 1).

89

Auxiliary Iq Current Command
[Aux Iq Command]

This parameter can be used to send an Iq
command (current reference) to the current limiter.
This command can passed as the total Iq
command, or can be added to the PI regulator
value (P121, Voltage Loop PI Output).

Parameter Type

Sink (Read/Write)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-120.0

Maximum Value

120

Related Parameters

P88, P90, P273

See Chapters

1, 9

The value entered into this parameter is used
only when ‘PI +Aux Cmd’ or ‘Aux Iq Cmd’ is
selected in the Iq Mode Select (when P90 = 1
or P90 = 2).

This parameter can receive the Iq command
from another RGU through P273 (RGU-to-RGU
Receive 1, Indirect 1).

90

Iq Mode Select
[Iq Mode Select]

This parameter selects the current reference input
to be passed to the current limiter.

Set this parameter to one of the values listed
below.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

3

Related Parameters

P89, P94, P121

Value Description

0

Lin PI Out

Selects the PI regulator output (P121). This is the normal selection for a standalone or master RGU.

1

PI + Aux Cmd Selects the PI regulator output value plus the Auxiliary Iq Command value (P121+P89). This allows P89 to be used as a trim value.

2

Aux Iq Cmd

Selects the Auxiliary Iq Command (P89). This is normally used by a slave RGU which is receiving its Iq commands from a master RGU.

3

No Iq Cmd

Selects 0 as the Iq Command