Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 164

Advertising
background image

Publication 2364F-5.01– October 2003

D-20

Programming Parameters

91

Iq Positive Current Limit
[Iq Pos Limit]

This parameter defines the active current limit
(positive).

This value is displayed as a percentage of the
Rated AC Line Current (P11).

Parameter Type

Sink (Read/Write)

Display Units

% of 11

Drive Units

Display Units * 5120/100

Factory Default

150.0

Minimum Value

10.0

Maximum Value

150.0

92

Iq Negative Current Limit
[Iq Neg Limit]

This parameter defines the active current limit
(negative).

This value is displayed as a percentage of the
Rated AC Line Current (P11).

Parameter Type

Sink (Read/Write)

Display Units

% of 11

Drive Units

Display Units * 5120/100

Factory Default

-150.0

Minimum Value

-150.0

Maximum Value

-10.0

93

Id Reference
[Id Reference]

This parameter displays the output of the reactive
current (Id) limiter.

This value is displayed as a percentage of the
Rated AC Line Current (P11).

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-60.0

Maximum Value

60.0

94

Iq Current Command
[Iq Command]

This parameter displays the Iq command being
sent to the Current Limiter.

This value may be determined by the PI regulator
and/or by an auxiliary Iq command from a master
RGU.

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-640.0

Maximum Value

640.0

Related Parameters

P89, P90, P121

The listing for P90 shows how the value for
this parameter is determined.

95

Filtered Iq Current Reference
[Filtered Iq Ref]

This parameter displays the filtered value of the Iq
Current Reference (P96).

This value is displayed as a percentage of the
Rated AC Line Current (P11).

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-150.0

Maximum Value

150.0

Related Parameters

P94, P96

P90

Iq Mode

Select

P121

Voltage
Loop PI

Output

P89

Auxiliary Iq

Command

0

+

+

PI Regulator

Current

Limiter

0

1

2

3

P94

Iq

Command

Σ

Lin PI Out

PI + Aux Cmd

Aux Iq Cmd

No Iq Cmd

0

1

2

3

Iq

Command

(from

Master RGU)

Advertising