Programming parameters d-13, Quick reference chart – Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 157

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-13

47

D/A Converter 1 Output
[DAC1 Output]
This parameter contains the value that is to be
sent to the digital-to-analog converter, then to
Analog Out 1 ( TB1-7, TB1-8 [com]).

The display value (-2048 to 2047) represents the
digital value, which is proportional to the voltage
sent through Analog Out 1 (-10V to +10V).

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-2048 (-10V signal)

Maximum Value

2047 (+10V signal)

Related Parameters

P49, P50, P51, P52

See Chapter

11

An external analog device can be wired to Analog
Out 1 (DAC1 Output), and can read the contents
of a parameter, selected by P49 (D/A Converter 1
Source).

The quick reference chart can be used to convert
the display value into the analog output voltage.

The diagram below shows how the source
parameter value is processed using P49, P50,
P51, P52, P47, then sent to the DAC for Analog
Out.

TB1

7

8

A

n

a

lo

g

O

u

t

1

A

n

a

lo

g

O

u

t

1

(

C

om

)

To Analog

Device

DAC1

Quick Reference Chart

-10

-8

-6

-4

-2

0

2

4

6

8

10

-2048

-1536

-1024

-512

0

512

1024

1536

2048

DAC Display Values

An

alog

Ou

tp

u

t V

o

ltag

e

(V

D

C

)

P49

DAC1

Indirect

P50

DAC1

Offset

P51

DAC1

Gain

P52

DAC1

Cutoff Freq

P47

DAC1

Output

+/- adjustment to value

in source parameter

multiplier to value in

source parameter

adjusts the

frequency

sends the resulting

value to Analog Out 1

determines

source parameter

Pxxx

Source

Parameter

Analog Out 1