Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 165

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-21

96

Iq Current Reference
[Iq Reference]

This parameter specifies the active current
reference (Iq) used by the current regulator loop.

This value is displayed as a percentage of the
Rated AC Line Current (P11).

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-150.0

Maximum Value

150.0

Related Parameters

P94, P95, P271

97

Net Positive Current Limit
[Net Iq Pos Limit]

This parameter displays the value of the positive
active current limit (Iq).

This value is displayed as a percentage of the
Rated AC Line Current (P11).

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

150.0

Minimum Value

10.0

Maximum Value

150.0

Related Parameters

P91, P98

98

Net Negative Current Limit
[Net Iq Neg Limit]

This parameter displays the value of the negative
active current limit (Iq).

This value is displayed as a percentage of the
Rated AC Line Current (P11).

Parameter Type

Source (Read Only)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

-150.0

Minimum Value

-10.0

Maximum Value

-150.0

Related Parameters

P91, P98

99

Iq Feedback Offset
[Iq Fbk Offset]

This parameter is used to offset the Iq feedback
value before it is stored in P100 (Iq Feedback),
and is used to offset the output of P96 (Iq
Reference) when it is passed to the current limiter.

Parameter Type

Sink (Read/Write)

Display Units

%

Drive Units

Display Units * 5120/100

Factory Default

0

Minimum Value

-2.4

Maximum Value

2.4

Related Parameters

P96, P100

Adjust this value to compensate for any offsets
in the system.

100

Iq Feedback
[Iq Feedback]

This parameter specifies the measured Iq
feedback (real or active current), displayed as a
percentage of the Rated AC Line Current (P11).
This value is used when calculating the Total Line
Current (P108).

Parameter Type

Sink (Read/Write)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-640.0

Maximum Value

640.0

Related Parameters

P96, P99, P106, P108

+ Motoring - Regenerating

P99

Iq

Feedback

Offset

Active

Current

Feedback

Current

Limiter

+

+

Σ

P96

Iq

Reference

P100

Iq

Feedback

+

+

Σ

Advertising