Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 159

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-15

52

D/A Converter 1 Frequency
[DAC1 Cutoff Freq]

This parameter determines the cutoff frequency
for the value being sent to DAC1 (which is
indicated by P49 [D/A Converter Source]). This
action is applied after the offset (P50) and gain
(P51).

To turn the filter off, set this to 0.

Parameter Type

Sink (Read/Write)

Display Units

R/S (rads/sec)

Drive Units

Display Units * 10

Factory Default

0 (Filter Off)

Minimum Value

0

Maximum Value

3276.7

Related Parameters

P47, P49, P50, P51

See Chapter

11

The P47 listing (D/A Converter 1 Output) shows
a diagram of the DAC process.

53

D/A Converter 2 Source
[DAC2 Indirect]

This parameter identifies the parameter value
which will be sent to DAC2 and out to Analog Out
2. The P48 listing (D/A Converter 2 Output)
shows a diagram of the DAC process.
The default selection is P108 (Total Line Current).

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

108 (Total Line Current)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P48, P54, P55, P56

See Chapter

11

54

D/A Converter 2 Offset
[DAC2 Offset]

This parameter determines the +/- adjustment
made to the value being sent to DAC2 (which is
indicated by P53 [D/A Converter Source]). This
offset is applied before the gain (P55).
The P47 listing (D/A Converter 1 Output) shows a
diagram of the DAC process.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-32767

Maximum Value

32767

Related Parameters

P48, P53, P55, P56

See Chapter

11

55

D/A Converter 2 Gain
[DAC2 Gain]

This parameter determines the gain adjustment
made to the value being sent to DAC2 (which is
indicated by P53 [D/A Converter Source]). This
gain is applied after the offset (P54).
The P47 listing (D/A Converter 1 Output) shows a
diagram of the DAC process.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 256

Factory Default

0.25

Minimum Value

-128.00

Maximum Value

128.00

Related Parameters

P48, P53, P54, P56

See Chapter

11

56

D/A Converter 2 Frequency
[DAC2 Cutoff Freq]

This parameter determines the cutoff frequency
for the value being sent to DAC2 (which is
indicated by P53 [D/A Converter Source]). This
action is applied after the offset (P54) and gain
(P55).
To turn the filter off, set this to 0.

Parameter Type

Sink (Read/Write)

Display Units

R/S (rads/sec)

Drive Units

Display Units * 10

Factory Default

0 (Filter Off)

Minimum Value

0

Maximum Value

3276.7

Related Parameters

P48, P53, P54, P55

See Chapter

11

The P47 listing (D/A Converter 1 Output) shows
a diagram of the DAC process.

57-59

P57-P59 are for internal use only.