Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 153

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-9

34

Host Status Word 2
[Host Status 2]

This parameter indicates a number of conditions
that the RGU is experiencing.

A condition is indicated by the bit being set to 1.
For example, the word, 1000 0011 0100 0000,

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P32, P33, P35

indicates that the RGU is regenerating current to
the AC line, the M1 contactor is closed, the DC
bus is at voltage, and the RGU control is active.

Bit

Description

0

Hard Fault

Indicates that a hard fault has occurred

1

Warning Flt

Indicates that a warning fault has occurred

2

pf Lagging

Indicates that the power factor is lagging (AC line voltage is lagging the current)

3

Iq Pos Limit

Indicates that the AC line active current (Iq) is at the positive limit

4

Iq Neg Limit

Indicates that the AC line active current (Iq) is at the negative limit

5

Ext ClrFault

Indicates that an external clear fault is required

6

Regen Cur

Indicates that the RGU is renerating current to the AC line

7

Ext Enable

Indicates that an external enable is activated

8

M1 Closed

Indicates that the main contactor M1 is closed

9

Bus at Volt

Indicates that the DC bus is at voltage

10

i2t Active

Indicates that the wire overtemperature monitor (i2t) is active

11

i2t Warning

Indicates that there is a wire overtemperature (i2t) warning

12-14 Not Used

15

Ctrl Running

Indicates that the RGU control is active

35

Host Mode
[Host Mode]

This parameter initiates the commands listed
below. To initiate commands, set each
appropriate bit to 1.
For example, to initiate the Error Limiter,
set P35 to 0000 0000 0000 0010.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 1000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P32, P33, P34

Bit

Description

0

Regen Only

Regenerative mode only (used with parallel NRU).

1

Err Limiter

Enables the Error Limiter.

2

Aux Limit

Activates the auxiliary limit as the current limit.

3

Linearizer

Activates the linearizer.

4-15

Not Used

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7