Publication 2364F-5.01– October 2003

Appendix

B

Specifications

Functional Specifications

Table B.1 Functional Specifications

Table B.2 Operating Sound Level

Efficiency

97%

AC Input Frequency Tolerance

45 to 65 Hz

AC Input Voltage Tolerance

±10%

Motoring Output Current Overload

150% of rated current for 60 seconds

Regenerating Output Current Overload

150% of rated current for 60 seconds

150% of rated current for 30 seconds
(380/460V AC N-code RGUs at 40°C,
or 575V AC N-code RGUs at 30°C)

Output Voltage Variation

10% maximum for a ±100% DC output current step
load change

Resolution of Output Voltage Selection

1.0V

Voltage Regulator Bandwidth

200 radians/sec maximum

Current Regulator Bandwidth

800 radians/sec (for 2 kHz units)
1200 radians/sec (for 4 kHz units)

RGU Current Code

Average Operating Sound Level (dB)

"

J

75

K

77

L

84

M

82

N

85

" Sound level determined using "A"-type weighting.

!

ATTENTION: Appropriate hearing protection must
be used in accordance with your company standards and
local ordinances. (OSHA dictates effective hearing
protection is to be administered when employees are
exposed to noise equal to or greater than an 8-hour

time-weighted average sound level of 85 decibels.)