Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 171

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-27

123

Voltage Mode Select
[Volt Mode Sel]

This parameter selects the source voltage
command used to produce the Bus Reference
(P128), which determines the voltage that the
RGU should supply to the bus.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

3

Minimum Value

0

Maximum Value

3

Related Parameters

P122, P126, P128, P129, P207

The bus rate limiter shown is used to limit limit the bus
reference from changing to rapidly. The output of this
limiter is the Bus Reference (P128).

124

Minimum Bus Reference
[Min Bus Ref]

This parameter defines the minimum voltage
command value that can be sent as a Bus
Reference (P128).

This value is calculated by the RGU and is 95%

Parameter Type

Source (Read/Write)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0.85 x P16

Minimum Value

0.85 x P16

Maximum Value

1.15 x P16

Related Parameters

P125, P126, P128, P129

of the greater of either the Nominal AC Line
Voltage (P10) multiplied by the square root of two,
or the Actual AC Line Volage (P14) multiplied by
the square root of two.

125

Maximum Bus Reference
[Max Bus Ref]

This parameter defines the maximum voltage
command value that can be sent as a Bus
Reference (P128).

This value is calculated by the RGU and is equal

Parameter Type

Source (Read/Write)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

1.13 x P16

Minimum Value

0.85 x P16

Maximum Value

1.15 x P16

Related Parameters

P124, P126, P128, P129

to 115% of the Nominal AC Line Voltage (P10)
multiplied by the square root of two.

126

Bus Rate Reference
[Bus Rate Ref]

This parameter specifies the bus voltage to be
achieved. The value of this parameter is passed
through the bus rate limiter to ensure that the DC
bus voltage does not change too rapidly, resulting
in the value for P128 (Bus Reference).

Parameter Type

Source (Read/Write)

Display Units

Volt

Drive Units

Display Units * 4096/P16

Factory Default

0.0

Minimum Value

0.85 x P16

Maximum Value

1.15 x P16

Related Parameters

P122, P123, P124, P125, P129, P127, P128

Value Description

0

Bus Volt Cmd Selects the P207 (Bus Voltage

Command) as the input. By default,
P207 is set to the Nominal DC Bus
Voltage (P16).

1

Aux Volt Cmd Selects the value entered into P122

(Auxiliary Voltage Command).

2

Bus&Aux Cmd Selects the sum of P207 and P122.

3

Bus Ref Auto Selects the bus reference calculated

from P10, P14, P16, and P130.

P123

Voltage

Mode

Select

0

1

2

3

Bus Volt Cmd

Aux Volt Cmd

Bus&Aux Cmd

Bus Ref Auto

0

1

2

3

B u s R a te

L im ite r

+

+

?

P122

Auxiliary

Voltage

Command

P207

Bus

Voltage

Command

P129

Bus

Reference
Automatic

P126

Bus Rate

Reference

R e f L im it

C a lc u la to r

P 14

P 16

P 10

P 130

P124/P125

Min/Max

Bus

Reference

Advertising