Publication 2364F-5.01– October 2003

12-4

Setting Up Trending

4.

5.

6.

If you want variable Y to be a:

Then:

Parameter value

Identify the parameter number of that parameter.

Constant value

Select a desired constant value in the range of +32767
to -32768.

If you have identified a parameter
number for variable Y and are
programming Trend:

Then enter the number of the parameter to be
sampled in:

1

P296

2

P308

3

P320

4

P332

If you have selected a constant
value for variable Y and are
programming Trend

Then:

1

1. Set P296 to"0".
2. Enter the desired constant value in P297.

2

1. Set P308 to"0".
2. Enter the desired constant value in P309.

3

1. Set P320 to"0".
2. Enter the desired constant value in P321.

4

1. Set P332 to"0".
2. Enter the desired constant value in P333.