Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 169

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-25

117

Voltage Loop Error Limit Gain
[PI Err Lim Gain]

This parameter specifies the gain to be applied in
the PI error limiter.

The P115 listing describes what the error limiter
does, and how it is activated.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 8

Factory Default

12.00

Minimum Value

0.00

Maximum Value

4096

Related Parameters

P115, P116

118

Voltage Loop Proportional Gain
[Iq Kp Gain]

This parameter specifies the proportional gain that
is applied to the Voltage Loop Error (P142).
The proportional (Kp) gain is adjusted to respond
to a change in load.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 8

Factory Default

15.00 (adjusted by RGU)

Minimum Value

0.00

Maximum Value

8100

Related Parameters

P119, P121, P142

The value of this parameter is adjusted by
the RGU. See P121 for more details.

119

Voltage Loop Integral Gain
[Iq Ki Gain]

This parameter specifies the integral gain that is
applied to the Voltage Loop Error (P142). The
integral gain is adjusted to remove any steady
state instabilities. After the gain from this
parameter is applied to P142, the result is stored
in P120.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 8

Factory Default

1500.00 (adjusted by RGU)

Minimum Value

0.00

Maximum Value

8100

Related Parameters

P118, P120, P121, P142

The value of this parameter is adjusted by
the RGU.

120

Voltage Loop Integrator Output
[Iq Integ Output]

This parameter displays the integral error
command, which is calculated from the Voltage
Loop Integral Gain (P119) and the Voltage Loop
Error (P142).

Parameter Type

Sink (Read/Write)

Display Units

% of P11

Drive Units

Display Units * 5120/100

Factory Default

0.0

Minimum Value

-640.0

Maximum Value

640.0

Related Parameters

P119, P121

The value of this parameter, which is displayed
as a percentage of P11 (Rated AC Line Current),
is used to determine the Voltage Loop PI Output
(P121). The listing for P121 shows how this
parameter is used in the PI regulator.