Installing Your RGU

Figure 7.5
Isolation Board (TB1 and TB3)

TB 1

TB 3

2

1

2

1

B urden R esistor

Phase T

B urden R esistor

Phase R

Phase T (LEM )

Phase T to

control board

Phase R (LEM )

Phase R to

control board

TB 2

2

1

B urden R esistor

Phase S

Phase S (LEM )

Phase S to

control board

(M and N -code

R G U s only)

Terminal Block

Terminal
Number

Recommended Wiring/Comments

TB1

(Main Control Board)

1, 2, 3, 4, 5,

6

14AWG. 80k differential input resistance. 40k com-

mon-mode input resistance.

7, 8, 9, 10

14AWG. Minimum 1k load resistance.

TB1, TB2, TB3

(Isolation Board)

1 and 2

Resistor sizes are listed in the electrical

specifications table (in Appendix A).

TB5

(Isolation Board)

1, 3, 4, 6, 8,

9

14AWG. 10mA load at 120V.

TB6

(Isolation Board)

1, 2, 3, 4

14AWG. Maximum 1A at 120V.