Electrical specifications – Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 134

Advertising
background image

Publication 2364F-5.01– October 2003

B-2

Specifications

Electrical Specifications

Table B.3 Electrical Specifications I

RGU

Current

Code

Nominal

Input

Voltage

(V AC)

" Continuous

AC Line

Current

(A AC)

Input

Power

(kVA)

Nominal DC
Bus Voltage

(V DC)

Maximum

Continuous DC

Bus Current

(A DC)

!Rated DC

Bus (kW)

Control Transformer Ratings

Basic

Capacity

(kVA)

Standard

Capacity

(kVA)

J

380

77

51

564

85

49

2.0

5.0

K

380

182

120

564

200

116

2.0

5.0

L

380

330

217

564

363

211

2.0

5.0

M

380

678

447

564

746

433

5.0

5.0

N

380

906

596

564

997

578

5.0

10.0

J

460

77

61

683

85

59

2.0

5.0

K

460

182

145

683

201

141

2.0

5.0

L

460

330

263

683

364

255

2.0

5.0

M

460

678

541

683

749

524

5.0

5.0

N

460

906

722

683

1000

700

5.0

10.0

J

575

77

62

848

88

74

2.0

5.0

K

575

182

181

848

201

170

2.0

5.0

L

575

286

285

848

326

276

2.0

5.0

M

575

602

600

848

686

582

5.0

5.0

N

575

802

799

848

914

775

5.0

10.0

" The continuous AC line current values apply to both motoring and regenerating operations.
! Rated DC bus kW is the power available on the DC thru bus at rated voltage and current.

Advertising