Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 160

Advertising
background image

Publication 2364F-5.01– October 2003

D-16

Programming Parameters

60

DSP DC Bus Voltage
[DSP DC Bus]

This parameter measures the DC bus voltage for
P143 (Scaled Bus Feedback) using the DSP.

This parameter is sent to P143 when DSP
Channel is selected in the Bus Voltage Input

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 4

Factory Default

0

Minimum Value

-8196

Maximum Value

8188

Related Parameters

P38, P61, P139, P143

Select (P139 = 1).

The displayed value of this parameter
corresponds to the drive units of P143.

The value of 4096 indicates that the bus voltage
feedback equals the Nominal DC Bus Voltage
(P16).

61

DSP Average Bus Voltage
[DSP Ave DC Bus]

This parameter sends the average DC bus voltage
from the DSP to P143 (Scaled Bus Feedback).

This parameter is only sent to P143 when DSP

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 4

Factory Default

0

Minimum Value

-8196

Maximum Value

8188

Related Parameters

P38, P60, P139, P143

Averaged is selected in the Bus Voltage Input

Select (P139 = 0).

The displayed value of this parameter corresponds to
the drive units of P143.

The value of 4096 indicates that the bus voltage
feedback equals the Nominal DC Bus Voltage (P16).

62

DSP Status Word
[DSP Status]

This parameter indicates the status of the DSP,
which is the processor used in the current loop.

A condition is indicated by the bit being set to 1.
For example, the word 0000 0001 0000 0000
indicates that the DSP is ready.

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P38, P60, P139, P143

Bit

Description

0-7

Not Used

8

DSP Ready

Indicates that the DSP is ready

9

DSP Running Indicates that the DSP is running

10

DSP Fault

Indicates that a DSP fault has occured

11-15 Not Used

63

P63 is for internal use only.

64

Current Loop Cross Couple Gain
[CrossCouple Gain]

This parameter indicates the cross couple gain
from the PI current regulator.

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

752

Minimum Value

0

Maximum Value

65535

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7