Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 186

Advertising
background image

Publication 2364F-5.01– October 2003

D-42

Programming Parameters

199

Current Loop Damping
[DSP Damping]

This parameter defines the damping used in the
current loop.

Parameter Type

Sink (Read/Write)

Display Units

%

Drive Units

Display Units * 1

Factory Default

100

Minimum Value

50

Maximum Value

200

Related Parameters

P198

200

Iq Reference Rate Limit
[Iq Change Rate]

This parameter defines the rate limit for the Iq
reference. This value is used by the current limiter
to prevent the Iq Reference (P96) from changing
too rapidly.

Parameter Type

Sink (Read/Write)

Display Units

% of P11

Drive Units

Display Units * 1

Factory Default

33.33

Minimum Value

2.44

Maximum Value

366.21

Related Parameters

P198

For example, a 575V AC M-code RGU, bydefault,
would not allow the Iq reference to change more than
200A (33.33% of 602A (P11)).

201

Per Unit Internal Capacitance Charge Rate
[Int Charge Rate]

This parameter indicates the charge rate of the
RGU internal capacitance.

To determine the rate, divide P16 (Nominal DC
Bus Voltage) by this value.

Parameter Type

Source (Read Only)

Display Units

msec

Drive Units

Display Units * 1

Factory Default

27

Minimum Value

0.00

Maximum Value

1000

Related Parameters

P202

202

Per Unit System Capacitance Charge Rate
[Sys Charge Rate]

This parameter indicates approximate charge rate
for the system capacitance.

To determine the rate, divide P16 (Nominal DC
Bus Voltage) by this value.

Parameter Type

Source (Read Only)

Display Units

msec

Drive Units

Display Units * 1

Factory Default

32

Minimum Value

0.00

Maximum Value

1000

Related Parameters

P201

203

External Capacitance
[Ext Capacitance]

This parameter specifies the estimated sum
capacitace of the all the AC units connected to the
DC bus. This value is used to calculate the
proportional and integral gains in the PI regulator
(P118 and P119).

Parameter Type

Sink (Read/Write)

Display Units

uF/10

Drive Units

Display Units * 1

Factory Default

9600

Minimum Value

10

Maximum Value

65000

Related Parameters

P202, P204

See Chapter/(Appendix)

8, (B)

See Appendix B for a listing of inverter capacitor
bank values.

Advertising