Interpreting and Setting Status, Command, and Fault Words

Table 10.1 Descriptions of Fault Status Bits

Fault Status Word 1 (P174-P176)

Bit

Description

0

ROM bad CRC

1

RAM error

2

Battery-backed RAM error

3

Error loading DSP software

4

Error loading FPGA software

5

I

q

foldback has occurred

6

M1 failure

7

SCANport error

8

RGU-to-RGU hardware error

9

Control voltage inadequate

10

Heatsink temperature is high

11

DC bus voltage less than minimum bus limit

12

DC bus voltage greater than maximum bus limit

13

Invalid data in battery-backed RAM

14

Bus failed to precharge

15

Host processor cannot connect to DSP processor

Fault Status Word 3 (P180-P182)

Bit

Description

0

Reset due to host clock loss

1

Reset due to host double bus fault

2

Watchdog reset

3

RGU power-up enabled

4

Battery low for battery-backed RAM

5

Primary control clock has been lost

6

RGU-to-RGU duplicate address

7

Slave RGU lost communications from Master RGU

8

Dual-port RAM error

9

DSP clock is no longer synchronized with host clock

10

Loss of fast task

11

Loss of background task

12

Address bus error

13

Data bus error

14

Line voltage is low

15

Line voltage is high

Fault Status Word 2 (P177-P179)

Bit

Description

0

Board-level desaturization

1

Board-level ground fault detected

2

Hardware-detected bus overvoltage

3

Hardware-detected bus overcurrent

4

Zero sequence errror

5

Phase-lock loop

6

Phase-loss error

7

RESERVED

8

RESERVED

9

RESERVED

10

Line overcurrent

11

Current offset

12

DSP processor not connecting to host

13

RESERVED

14

RESERVED

15

Unknown DSP processor error

Fault Status Word 4 (P183-P185)

Bit

Description

0

I

2t

approaching overload

1

I

2t

overload

2

Heatsink temperature high

3

Reset required

4

Heatsink sensor open, not connected

5

Heatsink sensor shorted

6

Master RGU has faulted

7

RESERVED

8

RESERVED

9

RESERVED

10

RESERVED

11

RESERVED

12

RESERVED

13

RESERVED

14

RESERVED

15

RESERVED