Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 33

Advertising
background image

Publication 2364F-5.01– October 2003

Overview

1-17

How does the RGU allow power to flow from the DC bus to the AC
line (regenerating mode of operation) and control the power
factor?

Commanding I

q

to be negative causes a phase shift in V

RGU

in

order to lead V

line

which regenerates power to the AC line. If I

d

is commanded to be 0, the RGU will operate at unity power
factor as shown in Figure 1.19, Figure 1.20, and Figure 1.21.

Figure 1.19
Regenerating Current Vector Diagram (Unity pf)

Figure 1.20
Voltage Vector Diagram

Notice that in Figure 1.21, V

line

is 180 degrees out of phase

with I

line

, and that the RGU is supplying power to the AC line.

Figure 1.21
Line Voltage and Current Waveforms (Unity pf, Iq < 0, Id = 0)

V

line

To Neutral

I

q

= I

line

0

Please note: XL*I

d

= 0

V

line

To Neutral

XL*I

q

V

RGU

V

line

To Neutral

I

line