Rgu standard features, Electrical system features, Packaging features – Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 38: Rgu standard features -22

Advertising
background image

Publication 2364F-5.01– October 2003

1-22

Overview

RGU Standard Features

RGU standard features include:

Electrical System Features

A 3-phase circuit breaker / motor circuit protector rated for
65kAIC:

•J, K, and L-code units have motor circuit protectors

•M-code units have circuit breakers

•N-code units have circuit breakers for control power with

motor-operated circuit breakers carrying rated bridge
current

AC line, current-limiting fuses rated at 600V AC with short
circuit protection rated at 65kAIC

AC line reactors in a quantity of 1 per phase

A "basic capacity" control power transformer that supplies ONLY
the RGU with single-phase, 115V AC control power

Primary and secondary control transformer fusing (excluding the
control bus fuse that is supplied with the "6P" control power
source upgrade option)

A "DC-Bus-Energized" pilot light that turns on when the bus
voltage is above 50V DC

A DC bus suppressor module

Utilization of #16AWG or #14AWG MTW (PVC insulated)
rated, stranded copper control wiring

Packaging Features

The Bulletin 2100 CENTERLINE motor control center (MCC)
packaging makes the RGU compatible with other Bulletin 2100
and 2300 products

Unit depth of 20" (J, K, L-code RGUs), overall unit depth of 25”
(M and N-code RGUs)

Ability to connect to other common DC bus MCC sections on
both the right and left sides

Top-entry AC line input

Removable top-plate for cutting conduit holes

Easy accessibility for routine maintenance

Advertising