Setting Up Trending

12-7

Setting the Number of Post
Samples

You also need to specify the number of data samples to be taken once
a trigger condition occurs. You can specify that 0 to 499 post samples
be taken. One sample is reserved for the instance when the trigger
condition becomes true.

Note: “Pre-samples” are samples taken prior to the trigger
condition becoming true.

Important: Typically, when a trend buffer is set to trigger on a fault,
you would set the post sample quantity to a lower value, such as 20.
This allows you to evaluate the trended parameter’s data from before
the trigger.


When a trend buffer is set up as a level detector, the post sample value
is generally set to a higher value. This allows you to evaluate what
happened after the trigger occurred.

1. Determine the number of samples to be taken after the trigger

point becomes true.

2.

Important: If the trigger condition occurs before the pre-

samples can be taken, the pre-samples may be
unreliable. The pre-samples are valid only if the
trigger does not occur before the pre-sample time
has elapsed. You can use the following equation to
determine pre-sample time:

T

1

= (500 – S

2

– 1) x R

S

T

1

pre-sample time

S

2

the number of post samples

R

S

the sample rate

If you are programming

Trend:

Then enter the post trigger samples in:

1

P300

2

P312

3

P324

4

P336