Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 175

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-31

147

Single Phase Detection Threshold
[1 Phase Threshold]

This parameter sets the threshold that a single
phase trip will occur. The Single Phase Detector
monitors the internal Phase Lock Loop (PLL) error
signal.

Parameter Type

Source (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

400

Minimum Value

100

Maximum Value

1000

Related Parameters

P148

A single phase trip occurs when the PLL error
exceeds the threshold set by P147 for a time
duration set by P148.

148

Single Phase Detection Delay Before Fault
[1 Phase Err Delay]

Time delay between detection of single phase
operation and the declaration of a fault.

Parameter Type

Source (Read/Write)

Display Units

SEL

Drive Units

Display Units * 200

Factory Default

3.0

Minimum Value

0.1

Maximum Value

60

Related Parameters

P147

149-150

P149-P150 are for internal use only.

151

Real Power
[Real Power]

This parameter indicates the real power being
supplied through the DC bus.

This value is calculated using the AC line voltage
(P14) and the active AC current

(P100 x P11).

Parameter Type

Source (Read Only)

Display Units

kW

Drive Units

Display Units * 1

Factory Default

0.0

Minimum Value

-3276.8

Maximum Value

3276.7

Related Parameters

P11, P14, P100

For example, if a K-code RGU has a 380V AC
line voltage in P14, and if P100 indicates that
the active current is 97% of the rated line
voltage (182A AC), then P151 would equal 67kW
(380 x 0.97 x 182 = 67kW).

152

Reactive Power
[Reactive Power]

This parameter indicates the reactive power being
supplied through the DC bus.

This value is calculated using the AC line voltage
(P14) and the reactive current

(P106 x P11).

Parameter Type

Source (Read Only)

Display Units

kVAR

Drive Units

Display Units * 1

Factory Default

0.0

Minimum Value

-3276.8

Maximum Value

3276.7

Related Parameters

P11, P14, P106

153

Apparent Power
[Apparent Power]

This parameter indicates the apparent power
being supplied through the DC bus.

This value is calculated using the Real Power
(P151) and the Reactive Power (P152).

Parameter Type

Source (Read Only)

Display Units

kVA

Drive Units

Display Units * 1

Factory Default

0.0

Minimum Value

0.0

Maximum Value

6553.5

Related Parameters

P151, P152

Advertising