Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 183

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-39

183

Host Fault Status Word 4
[Fault Status 4]

This parameter indicates a number of host fault
conditions.

1 - Fault

0 - No Fault

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P184, P185

P184 and P185 determine what conditions are
reported and how the conditions are to be
handled (warning/fault).

Bit

Description

0

I2t Warnings

Indicates that a warning has been detected by the I2t wire overload protect circuit.

1

I2t Overload

Indicates that an overload condition has been detected by the I2t wire overload protect circuit.

2

H/S HighTemp

Indicates that the RGU heatsink temperature is high (P87).

3

Reset Req’d

Indicates that the RGU must be reset (P32).

4

NTC Open

Indicates an NTC open condition.

5

NTC Short

Indicates an NTC short condition.

6

MSTR Faulted

Indicates that the master RGU is faulted (see P20).

7

1 Phase Warn

Indicates single phase condition has been detected (see P147).

8

1 Phase Err

Indicates single phase condition has persisted beyond time limit (see P148).

9-15

Not Used

184

Fault Status 4 Report Mask
[Flt Report Mask 4]

This parameter selects the faults that can be
reported to P180.

1 - Report

0 - Suppress

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1111 1111 1111 1111

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P183, P185

Bit

Description

0

I2t Warnings

Reports warnings from the I2t wire overload protector.

1*

I2t Overload

Reports overload conditions from the I2t wire overload protector.

2

H/S HighTemp

Reports high heatink temperatures (P87).

3*

Reset Req’d

Reports when a reset is required (P32).

4

NTC Open

Reports NTC open condition.

5

NTC Short

Reports NTC short condition.

6*

MSTR Faulted

Reports when the master RGU is faulted (P20).

7

1 Phase Warn

Reports single phase condition has been detected (see P147).

8

1 Phase Err

Reports single phase condition has persisted beyond time limit (see P148).

9-15

Not Used

* These items cannot be changed to zero.

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7