Programming Parameters

D-65

407

Signal Processor 2 Input
[SigProc 2 Input]

This parameter indicates the parameter that is to
be processed through Signal Processor 2.

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (no selection)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P408 to P411 (See also P402)

408

Signal Processor 2 Output
[SigProc 2 Output]

This parameter specifies where the results of the
processed value should be placed.

Parameter Type

Source (Read Only)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P407 to P411

409

Signal Processor 2 Gain
[SigProc 2 Gain]

This parameter specifies the gain that should be
applied to the source value (indicated in P407).

Note that the offset is applied before the gain.

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1.00

Minimum Value

-4.00

Maximum Value

4.00

Related Parameters

P407 to P411

410

Signal Processor 2 Offset
[SigProc 2 Offset]

This parameter specifies the offset to apply to the
source value (indicated in P407).

Note that the offset is applied before the gain.

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-32768

Maximum Value

32767

Related Parameters

P407 to P411

411

Signal Processor 2 Cutoff Frequency
[SigProc 2 Cutoff]

This parameter specifies the cutoff frequency to
be used by the signal processor.

Parameter Type

Source (Read Only)

Display Units

R/S (rad/sec)

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-32768

Maximum Value

32767

Related Parameters

P407 to P410

412

Signal Processor 3 Input
[SigProc 3 Input]

This parameter indicates the parameter that is to
be processed through Signal Processor 3.

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0 (no selection)

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P413 to P416 (See also P402)

413

Signal Processor 3 Output
[SigProc 3 Output]

This parameter specifies where the results of the
processed value should be placed.

Parameter Type

Source (Read Only)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P412 to P416