Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 189

Advertising
background image

Publication 2364F-5.01– October 2003

Programming Parameters

D-45

226

SCANport Clear Fault Mask
[Clear Fault Mask]

This parameter allows a connected SCANport
device to clear faults in the RGU. The selected
ports must be active (P224).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0111 1111

Minimum Value

0000 0000

Maximum Value

0111 1111

Related Parameters

P8, P224, P225, P227

Bit

Description

Bit

Description

0

RGU I/OClears RGU I/O faults

4

SCANport P:4Clears SCANport 4 faults

1

SCANport P:1Clears SCANport 1 faults

5

SCANport P:5Clears SCANport 5 faults

2

SCANport P:2Clears SCANport 2 faults

6

SCANport P:6Clears SCANport 6 faults

3

SCANport P:3Clears SCANport 3 faults

7

Not Used

227

SCANport Reset Mask
[Reset Mask]

This parameter allows a connected SCANport
device to reset the RGU. The selected ports must
be active (P224).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0111 1111

Minimum Value

0000 0000

Maximum Value

0111 1111

Related Parameters

P8, P224, P225, P226

Bit

Description

Bit

Description

0

RGU I/OResets RGU I/O

4

SCANport P:4Resets SCANport 4

1

SCANport P:1Resets SCANport 1

5

SCANport P:5Resets SCANport 5

2

SCANport P:2Resets SCANport 2

6

SCANport P:6Resets SCANport 6

3

SCANport P:3Resets SCANport 3

7

Not Used

228,229

P228 and P229 are for internal use only.

230

SCANport Disable Owner
[Disable Owner]

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0000 0111 1111

Related Parameters

P231, P232

Bit

Description

Bit

Description

0

RGU I/OIndicates that the RGU I/O port is disabled

4

SCANport P:4Indicates that the port for SCANport 4 is disabled

1

SCANport P:1Indicates that the port for SCANport 1 is disabled

5

SCANport P:5Indicates that the port for SCANport 5 is disabled

2

SCANport P:2Indicates that the port for SCANport 2 is disabled

6

SCANport P:6Indicates that the port for SCANport 6 is disabled

3

SCANport P:3Indicates that the port for SCANport 3 is disabled

7-15

Not Used

231

SCANport Enable Owner
[Enable Owner]

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0000 0111 1111

Related Parameters

P230, P232

Bit

Description

Bit

Description

0

RGU I/OIndicates that the RGU I/O port is enabled

4

SCANport P:4Indicates that the port for SCANport 4 is enabled

1

SCANport P:1Indicates that the port for SCANport 1 is enabled

5

SCANport P:5Indicates that the port for SCANport 5 is enabled

2

SCANport P:2Indicates that the port for SCANport 2 is enabled

6

SCANport P:6Indicates that the port for SCANport 6 is enabled

3

SCANport P:3Indicates that the port for SCANport 3 is enabled

7-15

Not Used