Publication 2364F-5.01– October 2003

Programming Parameters

D-37

179

Fault/Warning Select Mask 2
[Fault/Warn Mask2]

This parameter determines whether conditions
should be reported as a warning (0) or handled as
a fault (1).

The factory default, for example, shows that
all the usable bits cause faults.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1001 1100 0111 1111

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P174, P176

Bit

Description

Bit

Description

0*

Desaturizatn

Selects response to desaturization condition.

8

Not Used

1*

Board Intlk

Selects response to a board interlock condition.

9

Not Used

2*

HW Bus OverV Selects response to bus overvoltage (hardware).

10*

SW Line I

Selects response to line current condition (software).

3*

HW Line I

Selects response to current condtn (hardware).

11*

I Offset Err

Selects response to current offset error.

4*

Zero Seq Err

Selects response to zero sequence error.

12*

DualPort TO

Selects response to dual port timeout.

5*

Phase Lock L

Selects response to phase lock loop condition.

13

Not Used

6*

Phase Loss

Selects response to phase loss in AC line.

14

Not Used

7

Not Used

15*

DSP Fault

Selects response to DSP fault.

* These items cannot be changed to zero.

180

Host Fault Status Word 3
[Fault Status 3]

This parameter indicates a number of host fault
conditions.

1 - Fault

0 - No Fault

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P181, P182

P181 and P182 determine what conditions are
reported and how the conditions are to be
handled (warning/fault).

Bit

Description

0

Clock Loss

Indicates that a reset has occurred due to loss of oscillator.

1

Double Bus

Indicates a memory access error.

2

Watchdog

Indicates a expiration fault in the watchdog timer.

3

En at Pwr Up

Indicates that the RGU was Enabled at power up.

4

Battery Low

Indicates that the battery for the battery-backed memory is low.

5

TIO Loss

Indicates that the primary control loop clock has been lost.

6

R2R Dup Addr

Indicates that more than one RGU (in a parallel application) have the same R2R transmit address (P267).

7

Lost Master

Indicates that communication to the master has been lost.

8

DPRAM Error

Indicates a fault in the dual port between the host and DSP.

9

No Vloop Tic

Indicates that the voltage loop clock has been lost.

10

No Fast Task

Indicates that high speed control tasks have stopped.

11

No Bgnd Task

Indicates that background tasks are not executing.

12

Addr Bus Err

Indicates an error in the address bus.

13

Data Bus Err

Indicates an error in the data bus.

14

Line Low

Indicates that the AC line voltage has dropped below the AC Line Low Setting (P26).

15

Line High

Indicates that the AC line voltage has exceeded the AC Line High Setting (P27).

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7