Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 190

Advertising
background image

Publication 2364F-5.01– October 2003

D-46

Programming Parameters

232

SCANport Clear Fault Owner
[Clr Fault Owner]

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0000 0111 1111

Related Parameters

P230, P231

Bit

Description

Bit

Description

0

RGU I/OIndicates a clear fault is issued to RGU I/O

4

SCANport P:4Indicates a clear fault is issued to SCANport 4

1

SCANport P:1Indicates a clear fault is issued to SCANport 1

5

SCANport P:5Indicates a clear fault is issued to SCANport 5

2

SCANport P:2Indicates a clear fault is issued to SCANport 2

6

SCANport P:6Indicates a clear fault is issued to SCANport 6

3

SCANport P:3Indicates a clear fault is issued to SCANport 3

7-15

Not Used

233, 234

P233 and P234 are for internal use only.

235

Type 1 Status
[Type 1 Status]

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0000 1000 0001

Related Parameters

P236

Bit

Description

0

Enabled

1-6

Not Used

7

Faulted

8-15

Not Used

236

Type 2 Status
[Type 2 Status]

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0000 0000 0111

Related Parameters

P236

Bit

Description

0

Enabled

1

Warning

2

Faulted

3-15

Not Used

237,238

P237-P238 are for internal use only.

239

SCANport Remote Data In: P1
[Rem Data In:P1]

This parameter shows the value that is being
passed into SCANport 1 (J10).

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0.00

Minimum Value

0.00

Maximum Value

65535

Related Parameters

P224, P225