Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual

Page 146

Advertising
background image

Publication 2364F-5.01– October 2003

D-2

Programming Parameters

1

RGU Software Version
[Software Version]

This parameter shows the version of software that
is currently installed in the RGU.

Parameter Type

Source (Read Only)

Display Units

None

Drive Units

Display Units * 100

Factory Default

3.01

Minimum Value

0.00

Maximum Value

99.99

2

Password
[Password]

This parameter sets the user password.
To select ‘no password’, set this to zero.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

65535

3

Language Select
[Language Sel]

This parameter is used to select the display
language.

Value

Description

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

0

0

English

4

Frame Catalog Number
[Frame Catalog #]

This parameter stores the frame catalog number
of the RGU, describing the current code and input.
This value is used to configure P10, P11, P12,
and P16.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

11

Minimum Value

0

Maximum Value

15

Value Description

Value Description

0

Not Used

8

2364FA-LNB

(L-code, 460V AC)

1

2364FA-JNN

(J-code, 380V AC)

9

2364FA-LNC

(L-code, 575V AC)

2

2364FA-JNB

(J-code, 460V AC)

10

2364FA-MNN

(M-code, 380V AC)

3

2364FA-JNC

(J-code, 575V AC)

11

2364FA-MNB

(M-code, 460V AC)

4

2364FA-KNN

(K-code, 380V AC)

12

2364FA-MNC

(M-code, 575V AC)

5

2364FA-KNB

(K-code, 460V AC)

13

2364FA-NNN

(N-code, 380V AC)

6

2364FA-KNC

(K-code, 575V AC)

14

2364FA-NNB

(N-code, 460V AC)

7

2364FA-LNN

(L-code, 380V AC)

15

2364FA-NNC

(N-code, 575V AC)

5

RGU Control Mode
[RGU Control Mode]

This parameter is used to automatically configure
other parameters for a master-slave or a
standalone configuration.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

2

Minimum Value

0

Maximum Value

2

Related Parameters

None

Value Description

0

Master Mode

1

Slave Mode

2

Standalone

Advertising