Publication 2364F-5.01– October 2003

D-60

Programming Parameters

321

Trend 3 Y Value
[Trend Y Value]

This parameter defines a constant used to mask
the trend X operand (P318 or P319).

To use this parameter, the trend Y indirect (P320)
must equal zero.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

-32768

Maximum Value

32767

Related Parameters

P317 to P328 (See also P298)

322

Trend 3 Operator
[Trend Operator]

This parameter selects the operation to be
performed between trend X (P318 or P319) and
trend Y (P320 or P321). If trending is enabled
(P314), a true result of the operation will cause
the Trend 4 Input parameter value (from P317) to
be passed to the prescribed output (P328).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0 (GT)

Minimum Value

0

Maximum Value

7

Related Parameters

P317 to P328 (See also P298)

P298 (Trend 1 Operator) shows a sample
diagram of the trending configuration.

Value Description

Value Description

0

GTSelects the operation [Trend X must be greater than Trend Y].

4

ANDSelects the operation [Trend X AND Trend Y].

1

LTSelects the operation [Trend X must be less than Trend Y].

5

NANDSelects the operation [Trend X NAND Trend Y].

2

EQSelects the operation [Trend X must be equal to Trend Y].

6

ORSelects the operation [Trend X OR Trend Y].

3

NESelects the operation [Trend X must not be equal to Trend Y].

7

NORSelects the operation [Trend X NOR Trend Y].

323

Trend 3 Sample Rate
[Trend Samp Rate]

This parameter determines the rate of sampling
for the Trend 3 Indirects (P318, P320).

The value of this parameter can be changed in
increments of 0.002 sec.

Parameter Type

Sink (Read/Write)

Display Units

sec

Drive Units

Display Units * 2000

Factory Default

0.000

Minimum Value

0.000

Maximum Value

30.000

Related Parameters

P317 to P328 (See also P298)

324

Trend 3 Post Samples
[Trend Post Samp]

This parameter defines the number of samples
(out of 500) to be allocated for post-trigger
sampling.

Pre-samples + Post samples = 500 (0 to 499)

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

10

Minimum Value

0

Maximum Value

499

Related Parameters

P317 to P328 (See also P298)

325

Trend 3 Mode
[Trend Mode]

This parameter determines the duration of the
trending process. The trending process can be
configured to stop trending after a trigger event
occurs (default), or can continue trending.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0

Minimum Value

0

Maximum Value

1

Related Parameters

P317 to P328 (See also P298)

Value Description

0

One ShotCommands the trending process to stop after a single trigger event.

1

ContinuousCommands the trending process to run continuously.