Adjusting Voltage and Current Regulation Parameters

I

q

and I

d

Regulation

I

q

and I

d

perform PI current regulation.

PWM Saturation Regulation

The PWM saturation regulator monitors current distortion and adjusts
power factor compensation as required to maintain commanded bus
voltage and current.

DC to AC Transformation

DC to AC transformation converts DC equivalents into 3-phase AC
values for use in PWM.

AC to DC Transformation

AC to DC transformation converts 3-phase AC values into DC
equivalents for use in calculation.

Reference Angle Generation

The reference angle generator executes a phase-lock loop algorithm
to provide a reference angles that are in phase with those of the utility
3-phase AC line – line to neutral voltage.