Publication 2364F-5.01– October 2003

Overview

1-15

If I

d

were commanded to be equal to 0, V

RGU

would be

increased in magnitude and shifted closer toward V

line

(to

neutral) as shown in Figure 1.14, then we would have the
condition where the same amount of real current would be
flowing, but now I

d

would be equal to zero. I

line

would be

equal to I

q

and in phase with V

line

. The power factor is now

unity.

Figure 1.13
Motoring Current Vector Diagram (Unity pf)

Figure 1.14
Voltage Vector Diagram

Notice that in Figure 1.13 and Figure 1.15, V

line

and I

line

are in

phase with each other and that the RGU is supplying power to
the DC bus.

Figure 1.15
Motoring Line Voltage and Current Waveforms (Unity pf, Iq > 0, Id = 0)

V

line

To Neutral

I

q

= I

line

Please note: XL*I

d

= 0

V

RGU

V

line

To Neutral

XL*I

q

V

line

I

line