Your Current Code J RGU (Series A)

Table 2.1 Current Code J RGU Symbol to Component Cross Reference

AC 3-Phase Input Voltage

Symbol

Description

Option

"

380V AC

460V AC

575V AC

AM1

Ammeter monitoring L1

400A AC

MCP1

Motor Circuit Protector

150AHMCP

CH1- 3

Input line reactors

1193uH

1193uH

1853uH

CR2

Fault relay

2 NO/ 2 NC

CT1

Current transducer

100:5

CT1, 3 (EA1)

Current transducers (on EA1)

1000:1, 0-150A range

EA1

Power structure

EA2

Bus indicator PCB

EA3

Line RC suppressor PCB

EA4

DC bus suppressor assembly

EA10

Control power filter

For 4kHz carrier frequency

F1 (EA1)

DC bus fuse (on EA1)

125A

125A

120A

F1 (gate drv)

Power supply fuse (on gate driver PCB)

1A, KTK-R

F1 - 2 (EA2)

Bus indicator PCB fuses (on EA2)

1A, 1000V, KVR, 1-3/32" diameter, 3" length, 500AIC

F1 - 3

Incoming 3-phase, line fuses

125A, A70P

F4, F6

Primary fuse for a 2 kVA control

transformer

10A, KLDR

9A, KLDR

8A, KLDR

Primary fuse for a 5 kVA control

transformer

25A, KLDR

20A, KLDR

17.5A, KLDR

F7

RGU control power fuse

3.5A, KLDR

F8

Control bus fuse for a 5 kVA control
transformer

35A, FRN

F9, F10

Precharge fuses

10A, KLDR

10A, KLDR

15A, KLDR

F14 - 16

RC suppressor fuses

25A, KTK

F17 - 19

AC line sensor fuses

1A, KLDR

M1

Main contactor

110A

M2

Precharge contactor

12A

MTR1, 2

Door-mounted fan

7", 340CFM

PL1

DC-Bus-Energized pilot light

24V AC/DC, red, 800MR

PL2

Unit-Not-Faulted pilot light

115V AC, amber, 800MR

PT1

Control power transformer

A 2kVA control transformer is standard, and a 5kVA control transformer is
available as an option. This transformer has multiple taps to accomodate 380,
460, and 575 V AC primary voltages.

R13, R14

Precharge Resistors

6 ohm, 345 W

S11

Fault clear pushbutton

1 NO, 800MR

S12

Start switch

1 NO/ 1 NC, 800MR

SP1 - 3

Line-to-line MOVs

460 J, 320V AC

460 J, 320V AC

550 J, 385V AC

SP4

Neutral-to-ground MOV

760 J, 680V AC

760 J, 680V AC

760 J, 680V AC

TB1

Terminal Block

600V AC/DC, 22-14AWG, 10 terminals

TB2

Terminal Block

600V AC/DC, 22-14AWG, 2 terminals

TR1

Timer Relay

2 NO/ 2 NC (instantaneous), 1NO / 1 NC (on delay)

VM1

DC bus voltmeter

1000V DC

VM2

Ground fault detection

0-440V AC (meter), NO/NC contacts (relay)

" These components are provided with RGU standard options. Not all RGUs will have these components.