Programming Parameters

185

Fault/Warning Select Mask 4
[Fault/Warn Mask4]

This parameter determines whether conditions
should be reported as a warning (0) or handled as
a fault (1).

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

0000 0001 0111 1010

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Related Parameters

P183, P184

Bit

Description

0

I2t Warnings

Selects response to warnings detected by the I2t wire overload protect circuit.

1*

I2t Overload

Selects response to overload conditions detected by the I2t wire overload protect circuit.

2

H/S HighTemp

Selects response when the RGU heatsink temperature is high (P87).

3*

Reset Req’d

Selects response to reset required conditions (P32).

4

NTC Open

Selects response to NTC open condition.

5

NTC Short

Selects response to NTC short condition.

6*

MSTR Faulted

Selects response when the master RGU faults (see P20).

7

1 Phase Warn

Selects response when single phase condition has been detected (see P147).

8

1 Phase Err

Selects response when single phase condition has persisted beyond time limit (see P148).

9-15

Not Used

* These items cannot be changed to zero.

186-188

P186-P188 are for internal use only.

189

Auxiliary Relay Source
[Aux Relay Ind]

This parameter specifies the source to be used in
the logic operation shown in P191. This source
parameter will be masked with the value in P190
to determine if the auxiliary relay will change state.

Parameter Type

Sink (Read/Write)

Display Units

Parameter Number

Drive Units

Display Units * 1

Factory Default

33 (Host Status Word 1)

Minimum Value

0 (disabled)

Maximum Value

Maximum Defined Parameter Number

Related Parameters

P190, P191, P192

190

Auxiliary Relay Mask
[Aux Relay Mask]

This parameter defines the mask to be applied to
the value of the Auxiliary Relay Source parameter
(P189).

Press F3 to change the parameter display to
binary, hexadecimal, etc.

Parameter Type

Sink (Read/Write)

Display Units

None

Drive Units

Display Units * 1

Factory Default

1

Minimum Value

0

Maximum Value

65535

Related Parameters

P189, P191, P192

Bit

8

Bit

9

Bit
10

Bit
11

Bit
12

Bit
13

Bit
14

Bit
15

Bit

0

Bit

1

Bit

2

Bit

3

Bit

4

Bit

5

Bit

6

Bit

7