Chapter 11, Analog inputs, A/d value parameters – Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 113: Configuring analog input and output parameters, Analog inputs -1 a/d value parameters -1, Chapter

Publication 2364F-5.01– October 2003
Chapter
11
Configuring Analog Input and Output
Parameters
Analog Inputs
The RGU has two 14-bit, analog-to-digital convertors (A/D) rated to
receive user-configured analog inputs in the range of +/-10V DC.
The two A/Ds are labeled ADC0 and ADC1.
The A/Ds are not programmed and will clip voltage inputs that
exceed +10V or are less than -10V. When converted to digital values,
the A/D will output values in the range of +/-8192. A +10V input
equates to +8192, -10V to -8192.
The following A/D parameter contains the quantized equivalent of the
voltage applied at the analog input:
The analog input is accessible via terminal block 1 (TB1) on the main
control board as follows:
A/D Value Parameters
Use this parameter to view the quantized value of the voltage applied
at the analog inputs.
Description
ADC0 Parameter Number
ADC1 Parameter Number
Value after A/D conversion
36
37
ADC Name
Input
Terminal Designator
ADC0
(+)
TB1-2
(-)
TB1-1
ADC1
(+)
TB1-5
(-)
TB1-4