4.7.2

Monitoring of external events

Use the input DI_bSetExternError of the

LS_DriveInterface

system block to monitor external events

by means of corresponding logic operations and activate the error message "External error" in the

controller.

Parameterising a response to an external error
The controller response to the error message "External error" can be selected under

C00581

.

Activation of "External error" error message
The error message "External error" is activated by setting the input DI_bSetExternError to TRUE.

• After this, the error number for the error message "External error" "

0x20750000

" (when "Fault"

has been selected as response) will be stored in the internal fault memory (

C00168

).

Reset error message
The error message "External error" and other active error messages are reset by setting the input

DI_bResetError to TRUE.

• If the input DI_bSetExternError is still set to TRUE, the reset will not be carried out.
• Error messages can only be reset if the cause of the error has been eliminated.