5

Motor interface

5.8

Parameterisable additional functions

202

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Distribution of the interpolation points

• The saturation characteristic is defined by 17 interpolation points which are distributed linearly

on the x axis.

• Interpolation point 17 represents 100 % of the maximum motor current in the process (

C02855

).

[5-23] Saturation characteristic: Distribution of the interpolation points

Example for determining the saturation characteristic

Given values:

• Rated motor current: 5 A
• Maximum motor current: 20 A
• Maximum process current: 15 A (must be set later in

C00022

)

Procedure:

1. Deactivate correction (

C02859

= "OFF").

2. Set the maximum current up to which the motor is to be operated in the process in

C02855

(in

this example "15 A").

• The value set in

C02855

has to be greater or the same as

C00022

.

3. Adjust the current controller with different current setpoints and take down the corresponding

settings for Vp and Tn.

• The procedure for the adjustment is described in the chapter "

Optimising the current

controller

".

• The current setpoints that are to be set for the respective adjustment in

C00022

result from

the scaling of the maximum process current to the x axis of the saturation characteristic.

• The interpolation points which are required to define the saturation characteristic with a

sufficient quality varies from motor to motor and thus has to be determined individually.

0

6.25

12.5

18.75

25

31.25

37.5

43.75

50

56.25

62.5

68.75

75

81.25

87.5

93.75

100

I

max

Vp
Tn

[V/A]

[ms]

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

[%]

1