Parameter reference

14.2

Parameter list | C00973

828

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00973

C00974

C00975

C00976

C00977

Parameter | Name:

C00973 | VFC: Reset time - speed contr.

Data type: UNSIGNED_32

Index: 23602

d

= 5C32

h

From software version V3.0

V/f control

Setting range

(min. value | unit | max. value)

Lenze setting

1.0

ms

6000.0 6000.0 ms

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00974 | DC brake: Current

Data type: INTEGER_32

Index: 23601

d

= 5C31

h

From software version V3.0

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A

500.00 0.00 A

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100

Parameter | Name:

C00975 | DC brake: Current for quick stop

Data type: INTEGER_32

Index: 23600

d

= 5C30

h

From software version V3.0

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A

500.00 0.00 A

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100

Parameter | Name:

C00976 | DC brake: Activat. by quick stop

Data type: UNSIGNED_32

Index: 23599

d

= 5C2F

h

From software version V3.0

DC-injection braking

Selection list

(Lenze setting printed in bold)

0 Off
1 On

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00977 | Min. inh-time aft. overvolt

Data type: UNSIGNED_32

Index: 23598

d

= 5C2E

h

From software version V3.0

V/f control

Setting range

(min. value | unit | max. value)

Lenze setting

1

ms

10000 500 ms

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1