5

Motor interface

5.10

Internal interfaces | "LS_MotorInterface" system block

232

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Inputs

Identifier

DIS code | data type

Information/possible settings

MI_dnPosCtrlAdaptLoad_n

C02568/1

| DINT

Dynamic change of the proportional gain Vp of the position controller during

operation

For software versions lower than V5.0 the following applies:

Internal limitation to 10 ... 200 %

From software version V5.0 the following applies:

Internal limitation to 0 ... 200 %

MI_dnPosCtrlAdaptMotor_n

C02568/2

| DINT

Dynamic change of the proportional gain Vp of the phase controller during

operation

For software versions lower than V5.0 the following applies:

Internal limitation to 10 ... 200 %

From software version V5.0 the following applies:

Internal limitation to 0 ... 200 %

MI_dnSpeedCtrlAdapt_n

C02568/3

| DINT

Dynamic change of the proportional gain Vp of the speed controller during

operation

• If the input is assigned, the following applies:

V

P

= MI_dnSpeedCtrlAdapt_n [%] *

C00070

• If the input is not assigned, the following applies:

V

P

= 100 % *

C00070

=

C00070

• Internal limitation to 10 ... 200 %

Optimising the speed controller ( 147)

MI_bResetSpeedCtrlIntegrator

C02569/2

| BOOL

Reset integral action component in the speed controller

TRUE Integral action component is reset to "0".

MI_dnTorqueHighLimit_n

C02568/4

| DINT

MI_dnTorqueLowLimit_n

C02568/5

| DINT

Upper/lower limit value for correcting variable of the speed controller and total

torque setpoint

• These two inputs serve to select an external torque limitation.

• If the motor torque reaches the selected limits, the drive can no longer

follow the speed setpoint!

• If the torque limitation is active, the output MI_bTorqueSetpointLimited is

set to TRUE.

• 100 % ≡

C00057/2

• Only a positive torque is permissible as upper limit value.

• Only a negative torque is permissible as lower limit value.

• The motor mounting position (

C02527

) defines the assignment to the

limitation inputs of the motor control.

• The internally effective torque limit values are displayed in

C02559/1...2

.

MI_dnFluxSetpoint_n

C02568/7

| DINT

Setpoint for the field controller

MI_dnInertiaAdapt_n

C02568/8

| DINT

Adaptation of the moment of inertia in [%]

• If input is not assigned = 100 %

• Internal limitation to 0 ... 200 %

MI_dnBoostSet_n

C02568/9

| DINT

From V3.0

Boost voltage

• 100 % ≡ 1000 V

MI_bFlyingSyncBlocked

C02569/16

| BOOL

From V3.0

Block flying restart

Flying restart function ( 209)

FALSE Flying restart function is active

TRUE Flying restart process is blocked.