Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

227

5

Motor interface

5.9

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Failure of multiple motor phases during operation

This function is available from software version V10.0!

The following operating modes enable the detection of multiple motor phases during operation:

• VFCplus: V/f control closed loop
• SLVC: Sensorless vector control

The monitoring for failure of multiple motor phases is active if

1.

C00597

is set to a response other than "No response" (Lenze setting) and

2. the motor voltage exceeds the threshold value parameterised in

C02867

.

The "Motor disconnected" fault message is issued if the motor current is lower than the device-

dependent threshold value for > 20 ms.
The monitoring for failure of multiple motor phases can be deactivated if a value of 1000.0 V is

parameterised in

C02867

.