Braking operation

7.2

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

• When the utilisation reaches the limit value (100 %):

• The response set in

C00574

(default setting: "No response") is activated with the

corresponding effects on the state machine and the inverter.

Only applies to software versions lower than V3.0:

The activation of the brake chopper is reset to the permanently permissible mark-to space

ratio (taking the parameterised brake resistance into consideration). (The brake chopper is

activated with 4 kHz, which means that it can be switched on/off at minimum intervals of

250 μs.)

Stop!

The brake resistor can be thermally overloaded. Carry out protective measures suitable

for the installation, e.g.:

• Parameterisation of an error response in

C00574

and evaluation of the parameterised

error message within the application or within the machine control.

• External interconnection using the thermal contact on the brake resistor (e.g. supply

interruption via the mains contactor and activation of the mechanical brakes).

Note!

If the system is dimensioned correctly, this monitoring function should not respond. If

individual rated data of the actually connected brake resistor are not known, they have

to be determined "empirically".