5

Motor interface

5.6

V/f control (VFCplus)

194

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5. Evaluate the step response:

6. Change the gain Vp under

C00075

and the reset time Tn under

C00076

.

7. Repeat steps 4 ... 6 until the optimum step response of the motor current is reached.

• In the optimised state the current rise time typically is 0.5 ... 1 ms.

8. After the optimisation has been completed, deactivate the test mode again (

C00398

= "0:

Test mode deactivated").

9. If the Imin control is used, both calculated controller parameters can also be used for the

Imin controller:

C00075

C00958

(Imin controller: gain)

C00076

C00959

(Imin controller: reset time )

10. Save parameter set (

C00002

= "11: Save start parameters").

I

t

I

t

I

t

I

t

I

t

I

t

I

t

I

t

I

t

Vp < Vp opt.

Vp = Vp opt.

Vp > Vp opt.

Tn

<

T

n

opt.

Tn

=

T

n

opt.

Tn

>

T

n

opt.