Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

349

9

"CAN on board" system bus

9.10

Implemented CANopen objects | I-1018

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

I-1018

I-1029

This object serves to set the communication status to which the controller is to change after a bus

off, a node/life guarding event or a heartbeat event.

Index:

I-1018

Name:

Identity object

Subindex

Default setting

Display range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

see below

0

4294967295 ro

U32

1: Vendor ID
2: Product code
3: Revision number
4: Serial number

Subindex

Meaning

1

Manufacturer's identification number

• The identification number allocated to Lenze by the organisation "CAN in

Automation e. V." is "0x0000003B".

2

Product code

0x94001 9400 StateLine
0x94002 9400 HighLine / ServoPLC
0x94004 9400 regenerative power supply module

3

Main and subversion of firmware

4

Serial number

Index:

I-1029

Name:

Error behaviour

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

1

- (read access only)

ro

U8

1: Communication error

0

0

2 rw

U8

Subindex

Meaning

Lenze code

1

Status change after bus off, node/life guarding event or

heartbeat event:

C00625

0 State change from "Operational" to "Pre-

operational"

1 No state change
2 State change to "Stopped"