11.3.4

DC-injection braking

This function extension is available from software version V3.0!

Activate DC-injection braking
To activate DC-injection braking through the application, the bActivateDCBrake control input must

be set to TRUE.

• A change-over to the "Quick stop active" function state is effected and DC-injection braking with

the braking current set in

C00974

is carried out.

Flying restart process after cancelling DC injection braking
If the flying restart mode is activated in

C00990

and DC-injection braking is cancelled, a flying

restart process is automatically started to determine the current motor speed if the following

conditions are met:

• V/f control or sensorless vector control are selected as motor control in

C00006

.

• The position control structure is set to "Phase controller is active" in

C02570

.

• The MI_bFlyingSyncBlocked control input of the motor interface is not assigned or set to FALSE.
• The holding brake, if available, is not applied.

Note!

DC-injection braking is only possible if V/f control or sensorless vector control is selected

as motor control type in

C00006

!