5.9.3

Motor temperature monitoring

If the winding temperature detected by the motor temperature sensor exceeds the limit value set

in

C00121

, the response set in

C00584

is activated as advance warning.

• In the Lenze setting the "Warning" response occurs if the winding temperature exceeds 120 °C.
• As soon as the fixed limit value of 150 °C is exceeded, the response set in

C00583

is activated

(default setting: "Fault").

• If an open circuit is detected in the motor temperature sensor, the response set in

C00594

(default setting: "Fault") is activated.

Tip!
The winding temperature currently detected by the motor temperature sensor is displayed

in

C00063

.

Note!

By setting

C00583

= "0" the monitoring response and the temperature correction is

switched off within the motor control (identification and parameter correction)
This setting for example is reasonable if no usable winding temperature signal is

available.