I-1400/1, I-1400, 9"can on board" system bus – Lenze 9400 User Manual

Page 355

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

355

9

"CAN on board" system bus

9.10

Implemented CANopen objects | I-1400

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

I-1400

Communication parameter for receiving process data via RPDO1

[9-25] Data telegram assignment

How to change the identifier:

1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").

Index:

I-1400

Name:

RPDO1 communication parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

5

- (read access only)

ro

U8

1: COB-ID used by RPDO

0x200 + node ID

0

4294967295 rw

U32

2: transmission type

254

0

255 rw

U8

3: inhibit time

-

- (not used for RPDOs)

rw

U16

4: compatibility entry

-

- (reserved, read or write access leads to error message

0x06090011)

rw

U8

5: event timer

-

- (not used for RPDOs)

rw

U16

Subindex

Meaning

Lenze code

1

RPDO1 identifier

• The basic setting is according to the "Predefined

Connection Set": Identifier = 0x200 + node ID

C00321/1

2

RPDO Transmission type according to DS301 V4.02

Transmission type ( 308)

C00323/1

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

0/1

0/1

Extended identifier*

11-bit identifier

* The extended identifier is not supported. Bit 11 ... bit 29 must be set to "0".

Bit

Setting

Bit 30

0 RTR to this PDO possible (cannot be set).
1 RTR to this PDO not possible (Lenze).

Bit 31

0 PDO active
1 PDO inactive

Advertising
This manual is related to the following products: