Basic drive functions

11.12

Brake control

528

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Brake activation through time-out
If a waiting time for the brake activation > 0 s is set in

C02593

, the time monitoring is active, i. e. the

brake at the latest is activated for application after the waiting time has elapsed, even if the actual

speed value is still above the threshold for the brake activation set in

C02581

.

[11-34] Process of brake activation through time-out

Note!

In the Lenze setting the time monitoring is not active (

C02593

= "0 s").

 Speed setpoint

 Actual speed value

C02581

: Brake activation threshold

C02593

: Waiting time for brake activation

• The waiting time starts to elapse if the

speed setpoint has reached the threshold

for the brake activation.

• If the speed setpoint is still above the

threshold after the waiting time has

elapsed:

• The brake is automatically triggered to

close in automatic operation (mode 2/

12).

• The "brake activation via waiting time"

status is displayed at the BRK_dnState

status output via bit 23.

• The information "Motor brake:

Automatically activated after waiting

time has elapsed" is entered in the

logbook.

t

t

0

1

BRK_bReleaseBrakeOut

n



Œ

t

Standstill

t

Stopping