5motor interface – Lenze 9400 User Manual

Page 210

Advertising
background image

5

Motor interface

5.8

Parameterisable additional functions

210

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Sequence

[5-32] Process example: Speed follower is active  Controller inhibit  Controller enable

Flying restart process
The controller calculates the output frequency required for the momentary speed of the coasting

motor, then connects to the system, and accelerates the motor to the defined setpoint again.

• The flying restart process serves to prevent the motor from decelerating to zero speed with

subsequent acceleration.

• The currently detected flying restart speed is provided to the application via the current motor

speed MI_dnActualMotorSpeed_s.

A. Initial situation: basic function

"Speed follower" is enabled and

active.

B. The controller is inhibited while

the drive is not at standstill.

C. The motor coasts down

(torqueless).

D. The controller inhibit is

deactivated again.

E. The flying restart process starts.

t

t

t

Speed follower enabled

t

Speed setpoint

Speed follower active

Drive not ready

Actual

speed

CINH

0

1

2

3

4

Advertising